10 AWG aluminum voltage drop chart

59 ft at 30 ALongest 240 V single-phase run under 3% drop

V
A
ftDistance from the panel to the load, not round trip.

ResultsVoltage Drop

The short answer

10 AWG aluminum (10,380 circular mils) carrying 30 A on a 240 V single-phase circuit reaches 3% voltage drop at about 59 feet. At lighter loads it can go farther, as the tables below show.

Percent voltage drop at 240 V single-phase

Values over 3% are marked.

Load25 ft50 ft75 ft100 ft150 ft200 ft250 ft300 ft
5 A0.2%0.4%0.6%0.9%1.3%1.7%2.1%2.6%
10 A0.4%0.9%1.3%1.7%2.6%3.4%4.3%5.1%
15 A0.6%1.3%1.9%2.6%3.8%5.1%6.4%7.7%
20 A0.9%1.7%2.6%3.4%5.1%6.8%8.5%10.2%
25 A1.1%2.1%3.2%4.3%6.4%8.5%10.6%12.8%
30 A1.3%2.6%3.8%5.1%7.7%10.2%12.8%15.3%

Longest run that stays under 3%

Load120 V 1φ240 V 1φ208 V 3φ480 V 3φ
5 A176 ft353 ft353 ft814 ft
10 A88 ft176 ft176 ft407 ft
15 A59 ft118 ft118 ft271 ft
20 A44 ft88 ft88 ft204 ft
25 A35 ft71 ft71 ft163 ft
30 A29 ft59 ft59 ft136 ft

How it's calculated

Single-phase: VD = 2 × K × I × L ÷ CM Three-phase: VD = 1.732 × K × I × L ÷ CM K = 21.2 (aluminum), CM = 10,380 for 10 AWG

Table 310.16 lists 10 AWG aluminum at 25 A (60 °C) and 30 A (75 °C), before any 240.4(D) limit on the breaker size. Voltage drop is a separate check. On long runs it usually decides the wire size.

Other aluminum sizes

12 AWG · 8 AWG · 6 AWG · 4 AWG · 2 AWG · 3 AWG · 1 AWG · 1/0 AWG · 2/0 AWG · 3/0 AWG · 4/0 AWG

Open the full voltage drop calculator with these numbers

Results are estimates for planning and education. Verify against the current code edition your jurisdiction has adopted, manufacturer data and a licensed professional before you build or install.