14 AWG copper voltage drop chart

57 ft at 20 ALongest 240 V single-phase run under 3% drop

V
A
ftDistance from the panel to the load, not round trip.

ResultsVoltage Drop

The short answer

14 AWG copper (4,110 circular mils) carrying 20 A on a 240 V single-phase circuit reaches 3% voltage drop at about 57 feet. At lighter loads it can go farther, as the tables below show.

Percent voltage drop at 240 V single-phase

Values over 3% are marked.

Load25 ft50 ft75 ft100 ft150 ft200 ft250 ft300 ft
5 A0.3%0.7%1%1.3%2%2.6%3.3%3.9%
10 A0.7%1.3%2%2.6%3.9%5.2%6.5%7.8%
15 A1%2%2.9%3.9%5.9%7.8%9.8%11.8%
20 A1.3%2.6%3.9%5.2%7.8%10.5%13.1%15.7%

Longest run that stays under 3%

Load120 V 1φ240 V 1φ208 V 3φ480 V 3φ
5 A115 ft229 ft230 ft530 ft
10 A57 ft115 ft115 ft265 ft
15 A38 ft76 ft77 ft177 ft
20 A29 ft57 ft57 ft132 ft

How it's calculated

Single-phase: VD = 2 × K × I × L ÷ CM Three-phase: VD = 1.732 × K × I × L ÷ CM K = 12.9 (copper), CM = 4,110 for 14 AWG

Table 310.16 lists 14 AWG copper at 15 A (60 °C) and 20 A (75 °C), before any 240.4(D) limit on the breaker size. Voltage drop is a separate check. On long runs it usually decides the wire size.