What size wire for 60 amps at 100 feet?

4 AWG copper · 3 AWG aluminum240 V single-phase, 3% max drop, non-continuous load

V
A
ft
%
Auto uses 60 °C for 100 A and below, 75 °C above.

ResultsWire Size

The short answer

For a 60 amp load 100 feet from the panel on a 240 V single-phase circuit, use 4 AWG copper or 3 AWG aluminum. That keeps voltage drop at or under 3% and meets NEC Table 310.16 ampacity at the 60 °C terminal rating.

Ampacity decides the size here. The smallest copper wire rated for 60 A is 4 AWG, which would drop 1.55% over 100 ft, within the 3% guideline.

If the load is continuous (on for three hours or more, like heaters, EV chargers and lighting), the conductor must be rated for 125% of the load, or 75 A. That calls for 3 AWG copper.

60 amps at 100 feet on other systems

SystemCopperAluminumDrop (copper)
240 V single-phase4 AWG3 AWG1.55%
208 V three-phase4 AWG3 AWG1.54%
480 V three-phase4 AWG3 AWG0.67%

Three-phase systems carry the same current with less voltage drop, so they often allow a smaller conductor over the same distance.

60 amps at other distances (240 V copper)

DistanceCopper sizeGoverned by
25 ft4 AWGampacity
50 ft4 AWGampacity
75 ft4 AWGampacity
100 ft4 AWGampacity
150 ft4 AWGampacity
200 ft3 AWGvoltage drop
250 ft2 AWGvoltage drop
300 ft2 AWGvoltage drop

How this was calculated

Voltage drop = 2 × K × I × L ÷ CM = 2 × 12.9 × 60 × 100 ÷ 41,740 = 3.71 V (1.55% of 240 V)

K is 12.9 for copper and 21.2 for aluminum. CM is the conductor's area in circular mils. Distance is one-way. Change any input in the calculator above to check your own circuit.

These sizes assume no more than three current-carrying conductors in the raceway and 30 °C ambient. Derate under NEC 310.15 for more conductors or hotter locations, and size motor circuits under Article 430.

Open the full wire size calculator with these numbers

Results are estimates for planning and education. Verify against the current code edition your jurisdiction has adopted, manufacturer data and a licensed professional before you build or install.